Loading...
HomeMy WebLinkAboutOrdinance 56821 20251017_ms29 Ordinance No. 5682 Adoption of an Ordinance Repealing Chapter 15.04 of the Palo Alto Municipal Code and Adopting a New Chapter 15.04, the California Fire Code (2025 Edition) With Local Amendments and Related Findings The Council of the City of Palo Alto does ORDAIN as follows: SECTION 1. Title 15 of the Palo Alto Municipal Code is hereby amended by repealing in its entirety Chapter 15.04 and enacting a new Chapter 15.04 to read as follows: CHAPTER 15.04 CALIFORNIA FIRE CODE, CALIFORNIA CODE OF REGULATIONS, TITLE 24, PART 9 Sections 15.04.010 2025 California Fire Code, Title 24, Part 9 adopted and amended. 15.04.020 Local Amendments. 15.04.030 Section 102.5 Application of residential code. 15.04.040 Section 103.2 Appointment. 15.04.050 Sections 105.3.9 Permits/Permit fees. 15.04.060 Table 105.5.9 Permit amounts for compressed gases. 15.04.070 Table 105.5.22 Permit amounts for hazardous materials. 15.04.080 Section 105.5.25 and Sections 105.5.55 through 105.5.59 Operational permits. 15.04.090 Section 105.6.13 Hazardous materials and Section 105.6.26 Construction permits. 15.04.100 Reserved 15.04.110 Section 108.7 Certified Unified Program Agency Fees. 15.04.120 Section 109.1 Inspection authority. 15.04.130 Section 104.1.1 Enforcement/citation authority. 15.04.140 Section 113.4 Violation penalties. 15.04.150 Definitions Section 202 15.04.160 Section 316.7 Roof guiderails at interior courts. 15.04.170 320.3.13 Safety certification. 15.04.180 Section 322.6 Fire protection system. 15.04.190 Section 401.5 Making false report. 15.04.200 Section 503.1 Fire access roadways. Docusign Envelope ID: 9D422E8D-6457-425E-A365-25F0361FFDE4 2 20251017_ms29 15.04.210 Section 503.2.1 Dimensions. 15.04.220 Section 503.2.2 Authority. 15.04.230 Section 504.5 Access control devices. 15.04.240 Section 505.1.1 and 505.1.2 Premises identification. 15.04.250 Section 509.1.2 Fire protection equipment identification. 15.04.260 Sections 603.10 through 603.12. 15.04.270 Section 4103.1.2.1.1 Prohibitive locations. 15.04.280 Section 903.2 Automatic sprinkler systems, where required. 15.04.290 Section 903.3.1.1 NFPA 13 sprinkler systems. 15.04.295 Section 903.3.1.1.5 Increase in fire sprinkler design criteria. 15.04.300 Section 903.3.1.2 NFPA 13R sprinkler systems. 15.04.310 Section 903.3.1.3 and 903.3.1.3.1 NFPA 13D sprinkler systems. 15.04.320 Section 903.3.10 Floor control valves. 15.04.330 Section 905.3.1 Height. 15.04.340 Section 909.20.7 Maintenance and operational schedule. 15.04.350 Section 1008.3 Illumination required by an emergency electrical system. 15.04.360 Section 1031.2 Where required. 15.04.370 Section 1207.1.5 Large-scale fire test. 15.04.375 Section 1207.5.2 Maximum allowable quantities. 15.04.380 Section 1207.11.3 Location. 15.04.390 Section 3303.7 Fire walls. 15.04.400 Section 3307.1.2 and 3307.1.4. 15.04.410 Reserved. 15.04.420 Reserved. 15.04.430 Reserved. 15.04.435 Section 4103.1 Portable unvented heaters. 15.04.440 Section 5001.2.2.2 Health Hazards. 15.04.450 Section 5001.7 Hazard materials management plan electronic submissions. 15.04.460 Section 5003.1.3.1 Toxic, highly toxic, moderately toxic gases and similarly used or handled materials. 15.04.470 Section 5003.1.5 Other health hazards including carcinogens, irritants and sensitizers. 15.04.480 Section 5003.1.6 Additional secondary containment requirements. 15.04.490 Section 5003.2.2.1 Design and construction. 15.04.500 Section 5003.2.2.2 Additional regulations for supply piping for health hazard materials. Docusign Envelope ID: 9D422E8D-6457-425E-A365-25F0361FFDE4 3 20251017_ms29 15.04.510 Section 5003.3.1 Unauthorized discharges. 15.04.520 Section 5003.5.2 Ventilation ducting. 15.04.530 Section 5003.5.3 “H” Occupancies. 15.04.540 Section 5003.9.11 Fire extinguishing systems for workstations dispensing, handling or using hazardous materials. 15.04.550 Section 5003.10.4 Elevators utilized to transport hazardous materials. 15.04.560 Section 5004.2.1 Spill control for hazardous material liquids. 15.04.570 Sections 5004.2.2 and 5004.2.2.2 and Table 5004.2.2 Secondary containment for hazardous material liquids and solids. 15.04.580 Section 5004.2.3 Containment pallets. 15.04.590 Section 5704.2.7.5.8 Overfill prevention. 15.04.600 Section 5704.2.7.5.9 Automatic and/or remote filling of tanks. 15.04.610 Reserved. 15.04.620 Section 6001.1 Site scope. 15.04.630 Section 6002.1 Definitions. 15.04.640 Section 6004.1 Highly toxic, moderately toxic, and toxic compressed gases. 15.04.650 Sections 6004.2 and 6004.2.1 Indoor storage and use. 15.04.660 Section 6004.2.1.1 and Table 6004.2.1.1 Quantities. 15.04.670 Section 6004.4 through 6004.4.8.2 General indoor requirements. 15.04.010 2025 California Fire Code, Title 24, Part 9 adopted and amended. The California Fire Code, 2025 Edition, as adopted by the California Code of Regulations Title 24, Part 9, and Appendices B, C, D, E, F, G, H, and K is adopted as herein amended. One copy of the California Fire Code is on file and open to public inspection in the Office of the City Clerk. Additional copies of the secondary codes set forth within the California Fire Code, and the amendments set forth in this chapter, are on file and open to public inspection in the fire department administrative office. Whenever the phrase “California Fire Code” appears in this code or in any ordinance of the city, such phrase shall be deemed and construed to refer to and apply to the “California Fire Code, 2025 Edition” as adopted by the California Code of Regulations Title 24, Part 9 and as adopted and amended by this chapter. 15.04.020 Local Amendments. The provisions of this Chapter shall constitute local amendments to the cross-referenced provisions of the California Fire Code, 2025 Edition, and shall be deemed to replace the cross-referenced sections of said Code with the respective provisions set forth in this Chapter. Where used in this Chapter 15.04, ellipses shall indicate text of the California Fire Code, 2025 Edition, that has been Docusign Envelope ID: 9D422E8D-6457-425E-A365-25F0361FFDE4 4 20251017_ms29 adopted without amendment but is omitted for brevity. 15.04.030 Section 102.5 amended - Application of residential code. Section 102.5 of the California Fire Code is amended to read as follows: 102.5 Application of residential code. Where structures are designed and constructed in accordance with the California Residential Code, the provisions of this code shall apply as follows: 1.Construction and design provisions: a. Provisions of this code pertaining to the exterior of the structure shall apply, including, but not limited to, premises identification, fire apparatus access, and water supplies. b.Provisions of this code pertaining to the interior of the structure shall apply when specifically required by this code including, but not limited to, Sections 903.2 through 903.3.7 and Section 907.2.10. c.Where interior or exterior systems or devices are installed, construction permits required by Section 105.6 of this code shall also apply. 2.Administrative, operational, and maintenance provisions: all such provisions of this code shall apply. 15.04.040 Section 103.2 Appointment deleted. Section 103.2 of the California Fire Code is deleted. 15.04.050 Sections 105.3.9 Permits/Permit fees. Section 105.3.9 is added to the California Fire Code to read as follows: 105.3.9 Permits/Permit fees. All permit fees shall be established by the City Council as set forth in the municipal fee schedule. 15.04.060 Table 105.5.9 Permit amounts for compressed gases. Table 105.5.9 of the California Fire Code is amended to read as follows: TABLE 105.5.9 PERMIT AMOUNTS FOR COMPRESSED GASES1 Carbon dioxide used in carbon dioxide enrichment systems 875(100 lbs) Flammable (except cryogenic and liquefied petroleum gases) 200 Docusign Envelope ID: 9D422E8D-6457-425E-A365-25F0361FFDE4 5 20251017_ms29 For SI: 1 cubic foot = 0.0283m3. 1 Refer to Chapters 27, 30, 32, 35, 37, 40 and 41 for additional requirements and exceptions. 2 Cubic feet measured at normal Temperature and pressure. 15.04.070 Table 105.5.22 Permit amounts for hazardous materials. Table 105.5.22 of the California Fire Code is amended to read as follows: TABLE 105.5.22 PERMIT AMOUNTS FOR HAZARDOUS MATERIALS AMOUNT Carcinogens 10 pounds Combustible liquids See Section 105.5.16 Corrosive materials: Gases Liquids Solids See Section 105.5.8 55 gallons 500 pounds Gases Liquids See Section 105.5.8 See Section 105.5.16 Docusign Envelope ID: 9D422E8D-6457-425E-A365-25F0361FFDE4 6 20251017_ms29 Liquids Solids Any amount Liquids: Class I-IV Liquids: Class V Solids: Class I-IV Solids: Class V Any Amount No Permit Required Any Amount No Permit Required Gases Liquids 504 Cubic Feet Any amount Hazards: 55 gallons 500 pounds Gases Liquids Solids Any amount Any amount Any amount Gases Liquids Solids Any amount Any amount Any amount Gases Liquids Solids Any amount Any amount Any amount Liquids Solids Any amount For SI: 1 gallon = 3.785 L, 1 pound = 0.454kg. a.22 gallons when Table 5003.1.1(1) Note k applies and hazard identification signs in accordance with Section 5003.5 are provided for quantities of 22 gallons or less. b.220 pounds when Table 5003.1.1(1) Note k applies and hazard identification signs in accordance with Section 5003.5 are provided for quantities of 220 pounds or less. Docusign Envelope ID: 9D422E8D-6457-425E-A365-25F0361FFDE4 7 20251017_ms29 15.04.080 Section 105.5.25 and Sections 105.5.55 through 105.5.59 Operational permits. Section 105.5.25 of the California Fire Code is amended and Sections 105.5.60 through 105.64 are added to read as follows: [. . .] 105.5.25 Hot work operations. An operational permit is required for hot work including, but not limited to: 1. Public exhibitions and demonstrations where hot work is conducted. 2. Use of portable hot work equipment inside a structure. Exception: (deleted) 3. Fixed-site hot work equipment, such as welding booths. 4. Hot work conducted within a wildfire risk area. 5. Application of roof coverings with the use of an open-flame device. 6.Where approved, the fire code official shall issue a permit to carry out a hot work program. This program allows approved personnel to regulate their facility’s hot work operations. The approved personnel shall be trained in the fire safety aspects denoted in this chapter and shall be responsible for issuing permits requiring compliance with the requirements found in Chapter 35. These permits shall be issued only to their employees or hot work operations under their supervision. [. . .] 105.5.60 Liquid gas fueled equipment. An operational permit is required for liquid gas fueled equipment. 105.5.61 Battery operated equipment. An operational permit is required for commercial/industrial/research battery operated equipment. 105.5.62 Underground storage tank. An operational permit is required for Underground Storage Tanks. 105.5.63 Radioactive materials. An operational permit is required to store, use or handle any radioactive material or source. 105.5.64 Day care permit. An operational permit is required to operate a day care facility for more than six children or adults. Docusign Envelope ID: 9D422E8D-6457-425E-A365-25F0361FFDE4 8 20251017_ms29 15.04.090 Section 105.6.13 Hazardous materials and Section 105.6.26 Construction permits. Section 105.6.13 of the California Fire Code is amended, and 105.6.26 of the California Fire Code is added to read as follows: [. . .] 105.6.13 Hazardous Materials. A construction permit is required to install, repair damage to, abandon, remove, place temporarily out of service, or close or substantially modify a storage facility or other area regulated by Chapter 50 where the hazardous materials in use and when equipment is modified or installed that uses, stores, processes, or conveys hazardous materials. Exceptions: 1. deleted 2. For repair work performed on an emergency basis, application for permit shall be made within two working days of commencement work. [. . .] 105.6.26 Underground fire service lines: installation or modification. A construction permit is required for the installation, modification or removal from service of underground fire service lines. 15.04.100 Reserved 15.04.110 Section 108.7 Certified Unified Program Agency Fees. Section 107.7 is added to the California Fire Code to read as follows: 107.7 Certified Unified Program Agency (CUPA) Fees. Pursuant to the Participating Agency Agreement between the County of Santa Clara and the City of Palo Alto dated July 1, 1997, or as amended, the Fire Department is authorized to collect fees associated with the CUPA programs. The CUPA fees will be collected on an annual basis or as specified in the Palo Alto Municipal Fee Schedule. 15.04.120 Section 109.1 Inspection authority. Section 108.1 of the California Fire Code is amended to read as follows: 109.1 Inspection authority. The fire code official is authorized to inspect, as often as necessary, buildings and premises, including such other hazards or appliances designated by the fire code official for the purposes of ascertaining and causing to be corrected any Docusign Envelope ID: 9D422E8D-6457-425E-A365-25F0361FFDE4 9 20251017_ms29 conditions which would reasonably tend to cause fire or contribute to its spread, result in an unauthorized discharge of hazardous materials, or amount to any violation of this code or any other law or standard affecting fire and life safety. 15.04.130 Section 104.1.1 Enforcement/citation authority. Section 104.1.1 is added to the California Fire Code to read as follows: 104.1.1 Penal code citation authority. The employee positions designated in this section are authorized to exercise the authority provided in California Penal Code section 836.5 for violations of the California Fire Code. The designated employee positions are: Fire Chief, Deputy Fire Chief, Fire Marshal, Assistant Fire Marshal, Fire Inspector, Hazardous Materials Specialist and Hazardous Materials Inspector. 15.04.140 Section 113.4 Violation penalties. Section 112.4 of the California Fire Code is amended to read as follows: 113.4 Violation penalties. It is unlawful for any person to violate any provision or to fail to comply with any of the requirements of this Title 15 or any permits, conditions, or variances granted under this Title, and violators shall be subject to any penalty or penalties authorized by law, including but not limited to: administrative enforcement pursuant to Chapters 1.12 and 1.16 of the Palo Alto Municipal Code; and criminal enforcement pursuant to Chapter 1.08 of the Palo Alto Municipal Code. Each separate day or any portion thereof during which any violation of this chapter occurs or continues shall be deemed to constitute a separate offense. When the Fire Chief or his/her designee determines that a violation of this Chapter has occurred, the Fire Chief or his/her designee may record a notice of pendency of code violation with the Office of the County Recorder stating the address and owner of the property involved. When the violation has been corrected, the Fire Chief or his/her designee shall issue and record a release of the notice of pendency of code violation. [. . .] 15.04.150 Definitions Section 202 Except as noted herein, Section 202 is adopted in full. The following definitions are amended or added to Section 202 of the California Fire Code to read as follows: CORROSIVE LIQUID. Corrosive liquid is: 1)any liquid which, when in contact with living tissue, will cause destruction or Docusign Envelope ID: 9D422E8D-6457-425E-A365-25F0361FFDE4 10 20251017_ms29 irreversible alteration of such tissue by chemical action; or 2)any liquid having a pH of 2 or less or 12.5 or more; or 3)any liquid classified as corrosive by the U.S. Department of Transportation; or 4)any material exhibiting the characteristics of corrosivity in accordance with Title 22, California Code of Regulations §66261.22. EMERGENCY POWER OFF (EPO). A manually operated device that disconnects electrical services to the building or specific equipment. FALSE ALARM. The willful, knowing, or negligent initiation or transmission of a signal, message, or other notification of an event of fire when no such danger exists. LARGE-SCALE FIRE TESTING. Testing a representative energy storage system that induces a significant fire into the device under test and evaluates whether the fire will spread to adjacent energy storage system units, surrounding equipment, or through an adjacent fire-resistance-rated barrier. MAXIMUM THRESHOLD QUANTITY (MAX TQ). Maximum threshold quantity is the maximum quantity of a moderately toxic or toxic gas, which may be stored in a single vessel before a more stringent category of regulation is applied. The following equation shall be used to calculate the Max TQ: Max TQ (pounds) = LC50 (ppm) x 2 lb. MODERATELY TOXIC GAS. A moderately toxic gas is a chemical or substance that has a median lethal concentration (LC50) in air more than 2000 parts per million but not more than 7500 parts per million by volume of gas or vapor, when administered by continuous inhalation for an hour, or less if death occurs within one hour, to albino rats weighing between 200 and 300 grams each. HEALTH HAZARD -OTHER. A hazardous material which affects target organs of the body, including but not limited to, those materials which produce liver damage, kidney damage, damage to the nervous system, act on the blood to decrease hemoglobin function, deprive the body tissue of oxygen or affect reproductive capabilities, including mutations (chromosomal damage), sensitizers or teratogens (effect on fetuses). SECONDARY CONTAINMENT. Secondary containment is that level of containment that is external to and separate from primary containment and is capable of safely and securely containing the material, without discharge, for a period of time reasonably necessary to ensure detection and remedy of the primary containment failure. SPILL CONTROL. Spill control is that level of containment that is external to and separate from the primary containment and is capable of safely and securely containing the contents of the largest container and prevents the materials from spreading to other parts of the room. Docusign Envelope ID: 9D422E8D-6457-425E-A365-25F0361FFDE4 11 20251017_ms29 WORKSTATION. A workstation is a defined space or independent principal piece of equipment using hazardous materials with a hazard rating of 1. 15.04.160 Section 316.7 Roof guiderails at interior courts. Section 316.7 of the California Fire Code is added to read as follows: 316.7 Roof guardrails at interior courts. Roof openings into interior courts that are bounded on all sides by building walls shall be protected with guardrails. The top of the guardrail shall not be less than 42 inches in height above the adjacent roof surface that can be walked on. Intermediate rails shall be designed and spaced such that a 12-inch diameter sphere cannot pass through. 15.04.170 320.3.13 Safety certification. Section 320.3.13 of the California Fire Code is added to read as follows: 320.3.13 Safety certification. The equipment, process, training procedures and occupancy associated with industrial additive manufacturing may be required by the fire code official to receive a safety certification from Underwriter's Laboratory or equivalent. 15.04.180 Section 322.6 Fire protection system. Section 322.6 of the California Fire Code is added to read as follows: 322.6 Fire protection system. The storage and/or charging of power micromobility devices shall be protected with a NFPA 13 fire sprinkler system. The system shall be designed to Ordinary Hazard II. Exception: Micromobility powered devices in residential units. 15.04.190 Section 401.5 Making false report. Section 401.5 of the California Fire Code is amended to read as follows: 401.5 Making false report. A person shall not, knowingly or unknowingly, give, signal, or transmit a false alarm. Initiation or transmission in a twelve-month period of three or more signals, messages, or other notifications of an event of fire when no such danger exists shall be presumed negligent. 15.04.200 Section 503.1 Fire access roadways. Section 503.1 of the California Fire Code is amended to read as follows: Docusign Envelope ID: 9D422E8D-6457-425E-A365-25F0361FFDE4 12 20251017_ms29 503.1 Fire access roadways. Where required, fire apparatus access roads shall be provided and maintained in accordance with Sections 503.1.1 through 503.1.3 and as per Fire Department Access Road Standards. [. . .] 15.04.210 Section 503.2.1 Dimensions. Section 503.2.1 of the California Fire Code is amended to read as follows: 503.2.1 Dimensions. Fire apparatus access roads shall have an unobstructed width of not less than 20 feet (6096 mm) exclusive of shoulders, or as required by Appendix D, except for approved security gates in accordance with Section 503.6, and an unobstructed vertical clearance of 13 feet 6 inches (4115 mm). 15.04.220 Section 503.2.2 Authority. Section 503.2.2 of the California Fire Code is amended to read as follows: 503.2.2 Authority. The fire code official shall have the authority to require or permit modifications to the required access widths and/or vertical clearance where they are inadequate for fire or rescue operations or where necessary to meet the public safety objectives of the jurisdiction. 15.04.230 Section 504.5 Access control devices. Section 504.5 of the California Fire Code is amended to read as follows: 504.5 Access control devices. When access control devices including bars, grates, gates, electric or magnetic locks or similar devices, which would inhibit rapid fire department emergency access to within and throughout the building, are installed, such devices shall be approved by the fire code official. All electrically powered access control devices shall be provided with an approved means for deactivation or unlocking from a single location or otherwise approved by the fire code official or his/her designee. Access control devices must also comply with Chapter 10. 15.04.240 Section 505.1.1 and 505.1.2 Premises identification. Sections 505.1.1 and 505.1.2 of the California Fire Code are added to read as follows: 505.1.1 Address illumination. Address identification required by Section 505.1 shall be illuminated. Docusign Envelope ID: 9D422E8D-6457-425E-A365-25F0361FFDE4 13 20251017_ms29 505.1.2 Address identification size. Address numbers and letters required by Section 505.1 shall be sized as follows: 1. When the structure is between thirty-six (36) and fifty (50) feet from the road or other emergency means of access, a minimum of one-half inch (0.5”) stroke by six inches (6”) high is required. 2. When the structure is fifty (50) or more feet from the road or other emergency means of access, a minimum of one inch (1”) stroke by nine inches (9”) high is required. 15.04.250 Section 509.1.2 Fire protection equipment identification. Section 509.1.2 of the California Fire Code is added to read as follows: 509.1.2 Fire Protection equipment identification. Exterior fire control valves, standpipes, hose valves, fire department connection, post indicators, fire service backflow preventers and other fire department appurtenances are to be painted red for identification. 15.04.260 Sections 603.10 through 603.12. Section 603.10 through 603.12 is added to the California Fire Code to read as follows: 603.10 Immersion heaters. All electrical immersion heaters used in dip tanks, sinks, vats and similar operations shall be provided with approved over- temperature controls and low liquid level electrical disconnects. Manual reset of required protection devices shall be provided. 603.11 Electric vehicle service equipment – car chargers. Electric vehicle service equipment shall be equipped with collision protection and an emergency power off (EPO) switch as determined necessary by the Fire Code Official. 603.12 Enclosed parking manual exhaust system. Enclosed parking garages associated with non-residential buildings shall install a Knox remote power box to manually activate the mechanical ventilation system to 100% capacity. 15.04.270 Section 4103.1.2.1.1 Prohibitive locations. Section 4103.1.2.1.1 of the California Fire Code is amended to read as follows: 4103.1.2.1.1 Prohibitive Locations. The storage or use of portable outdoor gas- fired heating appliances is prohibited in any of the following locations: 1.Inside of any occupancy where connected to the fuel gas container. 2.Inside of tents, canopies and membrane structures. Docusign Envelope ID: 9D422E8D-6457-425E-A365-25F0361FFDE4 14 20251017_ms29 3.On exterior balconies and rooftops. Exception: intentionally deleted 15.04.280 Section 903.2 Automatic sprinkler systems, where required. Section 903.2 of the California Fire Code is amended to read as follows: 903.2 Automatic sprinkler systems, where required. Approved automatic sprinkler systems in new buildings and structures and in existing modified buildings and structures, shall be provided in the locations described in this section. Automatic fire sprinklers shall be installed per the requirements set forth in Sections 903.2.1 through 903.2.18 and as follows, whichever is the more restrictive: 1.An automatic sprinkler system shall be provided throughout all new buildings and structures. Exception: New non-residential occupancies, buildings or structures that do not exceed 350 square feet of building area and contain no interior plumbing fixtures. 2.An automatic sprinkler system shall be provided throughout all existing buildings when modifications are made that create conditions described in Sections 903.2.1 through 903.2.18, or that create an increase in fire area to more than 3,600 square feet or when the addition is equal or greater than 50% of the existing building square footage whichever is more restrictive. 3.An automatic fire sprinkler system is required in basements when any of the following occurs: a. New basements used for storage, utility, occupancy, or habitable space regardless of size. b. Existing basements that are altered for the use of storage, utility, occupancy, or habitable space regardless of size. c. Existing basements that are expanded by more than 50%. If the addition or alteration is only the basement, then only the basement is required to be protected by fire sprinklers. 4.An automatic fire sprinkler system is required when either the roof structure, exterior walls, or combination of both has been removed, altered and/or replaced in at least 50% of the existing structure. 5.An automatic sprinkler system shall be installed throughout when any change in use or occupancy creates a more hazardous fire/life safety condition, as determined by the Fire Chief. Docusign Envelope ID: 9D422E8D-6457-425E-A365-25F0361FFDE4 15 20251017_ms29 6.All new covered trash enclosures regardless of size require installation of fire sprinklers (nonresidential only). Exception: A fire extinguishing system will not be required when all of the following conditions are met: a. The trash enclosure, including the door(s) and roof are constructed of noncombustible materials. b. The trash enclosure is stand-alone structure, be a minimum of 20- feet away from adjacent buildings and 10-feet away from property line(s); and c. The enclosure is used exclusively for waste garbage, recyclables, and organize waste/composting contained within the approved trash bins/containers. No outdoor storage is permitted within the trash enclosure. 7. Phone booths and pods when installed in a commercial building equipped with a fire sprinkler system. 8. Fume hoods when installed in a commercial building equipped with a fire sprinkler system. Exception: Spaces or areas in telecommunications buildings used exclusively for telecommunications equipment, associated electrical power distribution equipment, batteries and standby engines, provided that those spaces or areas are equipped throughout with an automatic smoke detection system in accordance with Section 907.2 and are separated from the remainder of the building by not less than 1-hour fire barriers constructed in accordance with Section 707 or not less than 2-hour horizontal assemblies constructed in accordance with Section 711, or both. [. . .] 15.04.290 Section 903.3.1.1 NFPA 13 sprinkler systems. Section 903.3.1.1 of the California Fire Code is amended to read as follows: 903.3.1.1. NFPA 13 sprinkler systems. Where the provisions of this code require that a building or portion thereof be equipped throughout with an automatic sprinkler system in accordance with this section, sprinklers shall be installed throughout in accordance with NFPA 13 and State and local requirements except as provided in Section 903.3.1.1.1. Docusign Envelope ID: 9D422E8D-6457-425E-A365-25F0361FFDE4 16 20251017_ms29 15.04.295 903.3.1.1.5 Increase in fire sprinkler design criteria. Section 903.3.1.1.5 has been added to the California Fire Code to read as follows: 903.3.1.1.5 Increase in fire sprinkler design criteria. 1.For new buildings having no designated use or tenant, the minimum sprinkler design density shall be Ordinary Hazard Group II / 1500 square feet. 2.Where future use or tenant is determined to require a higher density, the sprinkler system shall be augmented to meet the higher density. 3.Light hazard shall be hydraulically designed to a 1500 square foot most remote area or as required by the fire code official. 4.Laboratory areas within buildings shall be hydraulically designed to Ordinary Hazard II density. 5.Parking areas where mechanical vehicle storage equipment is used the fire sprinkler system shall be hydraulically designed to Extra Hazard II density. 6.In multi-residential apartments, townhomes, and condominiums. 7.In new commercial buildings that will have electrical vehicle chargers, the fire sprinkler system shall be designed to Extra Hazard II density. 8.In new commercial buildings that will have power micromobility devices, the fire sprinkler system shall be designed to Ordinary Hazard II. 9.ESS in commercial buildings shall comply with one of the following: a. ESS units with a maximum stored energy capacity of 50 kWh, as described in Section 1207.5.1, shall be designed with a minimum density of 0.40 gpm/ft2 (1.14 L/min) based over the area of the room or 2,500 square-foot design area, whichever is smaller. b. ESS units (groups) exceeding 50 kWh shall use a density based on large-scale fire testing complying with Section 1207.1.7. [. . .] 15.04.300 Section 903.3.1.2 NFPA 13R sprinkler systems. Section 903.3.1.2 of the California Fire Code is amended to read as follows: 903.3.1.2 NFPA 13R sprinkler systems. Where allowed in buildings of Group R occupancies, automatic sprinkler systems shall be installed throughout in accordance Docusign Envelope ID: 9D422E8D-6457-425E-A365-25F0361FFDE4 17 20251017_ms29 with NFPA 13 and State and local standards. [. . .] 15.04.310 Section 903.3.1.3 and 903.3.1.3.1 NFPA 13D sprinkler systems. Section 903.3.1.3 of the California Fire Code is amended and 903.3.1.3.1 is added to read as follows: 903.3.1.2 NFPA 13D sprinkler systems. Where allowed, automatic sprinkler systems installed in one-and two-family dwellings shall be installed throughout in accordance with NFPA 13D and State and local standards. Fire sprinkler protection shall be provided under rear covered patios extending over 4 ft perpendicular from the exterior of the structure. 903.3.1.3.1 Increase in fire sprinkler design criteria. Structures determined by the fire code official to have higher firefighting hazardous condition, or located in the Wildland- Urban Interface Fire Area, shall have an increase in fire sprinkler design criteria as determined by the fire code official. 15.04.320 Section 903.3.10 Floor control valves. Section 903.4.3 of the California Fire Code is amended to read as follows: 903.3.10 Floor control valves. Automatic sprinkler systems serving buildings two (2) or more stories in height shall have valves installed to control the system independently on each floor including basements. 15.04.330 Section 905.3.1 Height. Section 905.3.1 of the California Fire Code is amended to read as follows: 905.3.1 Height. A Class I Standpipe System shall be installed in new buildings or buildings being retrofitted with a fire sprinkler system where the roof edge/parapet is greater than 27 feet above the lowest level of Fire apparatus access roadway and in below grade levels. 15.04.340 Section 909.20.7 Maintenance and operational schedule. Section 909.20.7 is added to the California Fire Code to read as follows: 909.20.7 Maintenance and operational schedule. A routine maintenance and operational testing program shall be initiated immediately after the smoke control system has passed the acceptance tests. A written schedule for routine maintenance and operational testing shall be established and both shall occur at least annually. Docusign Envelope ID: 9D422E8D-6457-425E-A365-25F0361FFDE4 18 20251017_ms29 15.04.350 Section 1008.3 Illumination required by an emergency electrical system. Section 1008.3 of the California Fire Code is amended to read as follows: Section 1008.3 Illumination required by an emergency electrical system. An emergency electrical system shall be provided to automatically illuminate the following areas in the event of a power supply failure: 1.In rooms or spaces that require two or more exits or access to exits: 1.1. Aisles. 1.2. Corridors. 1.3. Exit access stairways and ramps. 2.In buildings that require two or more exits or access to exits: 2.1. Interior exit access stairways and ramps. 2.2. Interior and exterior exit stairways and ramps. 2.3. Exit passageways. 2.4. Vestibules and areas on the level of discharge used for exit discharge in accordance with Section 1028.2. 2.5. Exterior landings as required by Section 1010.1.5 for exit doorways that lead directly to the exit discharge. 2.6 Group I-2 exit discharge stairways, ramps, aisles, walkways and escalators leading to a public way or to a safe dispersal area in accordance with Section 1028.5. 3.In other rooms and spaces: 3.1. Electrical equipment rooms. 3.2. Fire command centers. 3.3. Fire pump rooms. 3.4. Generator rooms. 3.5. Public restrooms. 15.04.360 Section 1031.2 Where required. Section 1031.2 of the California Fire Code is amended to read: 1031.2 Where required. In addition to the means of egress required by this chapter, emergency escape and rescue openings shall be provided in Group R occupancies: Basements and sleeping rooms below the fourth story above grade plane shall have not fewer than one emergency escape and rescue opening in accordance with this section. Where basements contain one or more sleeping rooms, an emergency escape and rescue opening shall be required in each sleeping room but shall not be required in adjoining areas of the basement. Such openings shall open directly into a public way or to a yard or court that opens to a public way or to an egress balcony that leads to a public way. Docusign Envelope ID: 9D422E8D-6457-425E-A365-25F0361FFDE4 19 20251017_ms29 Exceptions: 1.In Groups R-1 and R-2 occupancies constructed of Type I, Type IIA, Type IIIA or Type IV construction equipped throughout with an approved automatic sprinkler system in accordance with Section 903.3.1.1. 2.Group R-2.1 occupancies meeting the requirements for delayed egress in accordance with Section 1010.2.13 may have operable windows that are breakable in sleeping rooms permanently restricted to a maximum of 4-inch open position. 3.Emergency escape and rescue openings are not required from basements or sleeping rooms that have an exit door or exit access door that opens directly into a public way or to a yard, court or exterior egress balcony that leads to a public way. 4.Storm shelters and basements used only to house mechanical equipment not exceeding a total floor area of 200 square feet (18.58 m2) 15.04.370 Section 1207.1.5 Large-scale fire test. Section 1207.1.5 of the California Fire Code is amended to read: 1207.1.5 Large-scale fire test. Where required elsewhere in Section 1207, large-scale fire testing shall be conducted in accordance with NFPA 855 as amended, and UL 9540A. The testing shall be conducted or witnessed and reported by an approved testing laboratory and show that a fire involving one ESS will not propagate to an adjacent ESS, and where installed within buildings, enclosed areas and walk-in units will be contained within the room, enclosed area or walk-in unit for a duration equal to the fire-resistance rating of the room separation specified in Section 1207.7.4. The test report shall be provided to the fire code official for review and approval in accordance with Section 104.822. 15.04.375 Section 1207.5.2 Maximum allowable quantities. Section 1207.5.2 of the California Fire Code is amended to read as follows: 1207.5.2 Maximum allowable quantities. Fire areas within rooms, areas and walk-in units containing electrochemical ESS shall not exceed the maximum allowable quantities in Table 1207.5. The allowable number of fire areas, maximum allowable quantity, and fire-resistance rating of fire-barriers for commercial structures shall comply with Table 1207.5.1. Exceptions: Where approved by the fire code official, rooms, areas and walk-in units containing Docusign Envelope ID: 9D422E8D-6457-425E-A365-25F0361FFDE4 20 20251017_ms29 electrochemical ESS that exceed the amounts in Table 1207.5 shall be permitted based on a hazardous mitigation analysis in accordance with Section 1207.1.6 and large-scale fire testing complying with Section 1207.1.7. 1.Lead-acid and nickel-cadmium battery systems installed in facilities under the exclusive control of communications utilities and operating at less than 50 VAC and 60 VDC in accordance with NFPA 76. 2.Dedicated-use buildings in compliance with Section 1207.7.1. TABLE 1207.5.1 DESIGN AND NUMBER OF ESS FIRE AREAS STORY PERCENTAGE OF MAXIMUM ALLOWABLE QUANTITY PER FIRE AREAS PER STORY FIRE-RESISTANCE RATING FOR FIRE BARRIERS IN HOURS 7-9 6 5 4 3 2 50 50 50 75 100 100 2 2 2 4 6 6 2 2 2 2 2 2 2 50 2 3 15.04.380 Section 1207.11.3 Location. Section 1207.11.3 of the California Fire Code is amended to read: 1207.11.3 Location. ESS shall be installed only in the following locations: 1.Detached garages and detached accessory structures. 2.Attached garages separated from the dwelling unit living space and sleeping units in accordance with Section R302.6. 3.Outdoors or on the exterior side of the exterior walls located not less than 3 feet (914 mm) from doors and windows directly entering the dwelling unit and shall not be located below or above any emergency escape and rescue openings. 4.Enclosed utility closets, basements and storage or utility spaces within dwelling Docusign Envelope ID: 9D422E8D-6457-425E-A365-25F0361FFDE4 21 20251017_ms29 units and sleeping units with finished or noncombustible walls and ceilings. Walls and ceilings of unfinished wood-framed construction shall be provided with not less than 5/8-inch (15.9 mm) Type X gypsum wallboard. 5.ESS shall not be installed in sleeping rooms, or in closets, or spaces opening directly into sleeping rooms or in habitable spaces of dwelling units. 15.04.390 Section 3303.7 Fire walls. Section 3305.9 is added to the California Fire Code to read as follows: 3303.7 Fire walls. When firewalls are required in combustible construction, the wall construction shall be completed (with all openings protected) immediately after the building is sufficiently weather-protected at the location of the wall(s). 15.04.400 Section 3307.1.2, 3307.1.4. Section 3312.1 of the California Fire Code is amended to read as follows: 3307.1.2 Stairways required. Each level above the first story in new multi-story buildings be provided with at least two usable exit stairways after the floor decking is installed. The stairways shall be continuous and shall discharge to grade level. Stairways serving more than two floor levels shall be enclosed (with openings adequately protected) after exterior walls/windows are in place. Exit stairs in new and in existing, occupied buildings shall be lighted and maintained clear of debris and construction materials at all times. Exception: For new multi-story buildings, one of the required exit stairs may be obstructed on not more than two contiguous floor levels for the purposes of stairway construction (i.e., installation of gypsum board, painting, flooring, etc.). 3307.1.4 Required means of egress. All new buildings under construction shall have a least one unobstructed means of egress. All means of egress shall be identified in the written site safety plan as required by Section 3303.1. 15.04.410 Reserved 15.04.420 Reserved 15.04.430 Reserved 15.04.435 Section 4103.1 Portable unvented heaters. Section 4103.1 of the California Fire code is amended to read as follows: 4103.1 Portable unvented heaters. Portable unvented fuel-fired heating equipment Docusign Envelope ID: 9D422E8D-6457-425E-A365-25F0361FFDE4 22 20251017_ms29 shall be prohibited in occupancies in Groups A, B, E, I, R-1, R-2, R-2.1, R-2.2, R-3, R-3.1 and R-4 and ambulatory care facilities. Exceptions: 1.Portable unvented fuel-fired heaters listed and labeled in accordance with UL 647 are permitted to be used in one- and two-family dwellings, where operated and maintained in accordance with the manufacturer’s instructions. 2.Portable outdoor gas-fired heating appliances in accordance with Section 4103.1.2. 15.04.440 Section 5001.2.2.2 Health Hazards. Section 5001.2.2.2 of the California Fire Code is amended to read as follows: 5001.2.2.2 Health Hazards. The material categories listed in this section are classified as health hazards. A material with a primary classification as a health hazard can also pose a physical hazard. 1.Highly toxic, toxic and moderately toxic. 2.Corrosive materials. 3.Moderately toxic gas. 4.Health hazards-Other. 15.04.450 Section 5001.7 Hazard materials management plan (HMMP) electronic submissions. Section 5001.7 is added to the California Fire Code to read as follows: 5001.7 HMMP electronic submissions. Each applicant for a permit, a renewed permit, or an amended permit pursuant to this title shall file an electronic submission of all hazardous materials through California Environmental Reporting System (CERS) for the fire chief's approval, to be known as a hazardous materials management plan (HMMP), which shall demonstrate the suitable storage of hazardous materials. The HMMP may be amended at any time with the consent of the fire chief. The HMMP shall be a public record except as otherwise specified. Section 18.23.100 in Title 18 identifies notification requirements of the availability of the HMMP. Approval of the HMMP shall mean that the HMMP has provided adequate information for the purposes of evaluating the permit approval. Such approval shall not be understood to mean that the city has made an independent determination of the adequacy of that which is described in the HMMP electronic submission. 15.04.460 Section 5003.1.3.1 Toxic, highly toxic, moderately toxic gases and similarly used Docusign Envelope ID: 9D422E8D-6457-425E-A365-25F0361FFDE4 23 20251017_ms29 or handled materials. Section 5003.1.3.1 is added to the California Fire Code to read as follows: 5003.1.3.1 Toxic, highly toxic, moderately toxic gases and similarly used or handled materials. The storage, use, and handling of toxic, highly toxic and moderately toxic gases in amounts exceeding Table 6004.2 or 6004.3 shall be in accordance with this Chapter and Chapter 60. Any toxic, highly toxic or moderately toxic material that is used or handled as a gas or vapor shall be in accordance with the requirements for toxic, highly toxic or moderately toxic gases. 15.04.470 Section 5003.1.5 Other health hazards including carcinogens, irritants and sensitizers. Section 5003.1.5 is added to the California Fire Code to read as follows: 5003.1.5 Other health hazards including carcinogens, irritants and sensitizers. The storage, use, and handling of materials classified as other health hazards including carcinogens, irritants and sensitizers in amounts exceeding 810 cubic feet for gases, 55 gallons for liquids and 5,000 pounds for solids shall be in accordance with this Section 5003. 15.04.480 Section 5003.1.6 Additional secondary containment requirements. Section 5003.1.6 is added to the California Fire Code to read as follows: 5003.1.6 Additional secondary containment requirements. In addition to the requirements set forth in Section 5004.2, an approved containment system is required for any quantity of hazardous materials that are liquids or solids at normal temperature and pressure (NTP), where a spill is determined to be a plausible event and where such an event would endanger people, property or the environment. The approved containment system may be required to include a combination of spill control and secondary containment meeting the design and construction requirements set forth in section 5004.2. 15.04.490 Section 5003.2.2.1 Design and construction. Section 5003.2.2.1 of the California Fire Code is amended to read as follows: 5003.2.2.1 Design and construction. Piping, tubing, valves, fittings and related components used for hazardous materials shall be in accordance with the following: 1.Piping, tubing, valves, fittings and related components shall be designed and fabricated from materials compatible with the material to be contained and shall be of adequate strength and durability to withstand the pressure, structural and Docusign Envelope ID: 9D422E8D-6457-425E-A365-25F0361FFDE4 24 20251017_ms29 seismic stress, and exposure to which they are subject. 2.Piping and tubing shall be identified in accordance with ASME A13.1 and the Santa Clara County Fire Chiefs Marking Requirements and Guidelines for Hazardous Materials and Hazardous Waste to indicate the material conveyed. 3.Manual valves or automatic remotely activated fail-safe emergency shutoff valves shall be installed on supply piping and tubing and provided with ready access at the following locations at the following locations: a.The point of use. b.The tank, cylinder or bulk use. 4.Manual emergency shutoff valves and controls for remotely activated emergency shutoff valves shall be clearly visible, provided with ready access and identified in an approved manner. 5.Backflow prevention or check valves shall be provided when the backflow of hazardous materials could create a hazardous condition or cause the unauthorized discharge of hazardous materials. 6.Where gases or liquids having a hazard ranking of: Health hazard Class 3 or 4 Flammability Class 4 Reactivity Class 4 In accordance with NFPA 704 are carried in pressurized piping above 15 pounds per square inch gauge (psig)(103 Kpa), an approved means of leak detection, emergency shutoff or excess flow control shall be provided. Where the piping originates from within a hazardous material storage room or area, the excess flow control shall be located within the storage room or area. Where the piping originates from a bulk source, the excess flow control shall be located as close to the bulk source as practical. Exceptions: a.Piping for inlet connections designed to prevent backflow. b.Piping for pressure relief devices. 7.Secondary containment or equivalent protection from spills or leaks shall be provided for piping for liquid hazardous materials and for highly toxic and toxic corrosive gases above threshold quantities listed in Tables 6004.2 and 6004.3. Secondary containment includes, but is not limited to, double- walled piping. Exceptions: a. Secondary containment is not required for toxic corrosive gases if the piping is Docusign Envelope ID: 9D422E8D-6457-425E-A365-25F0361FFDE4 25 20251017_ms29 constructed of inert materials. b.Piping under sub-atmospheric conditions if the piping is equipped with an alarm and fail-safe-to-close valve activated by a loss of vacuum. 8.Expansion chambers shall be provided between valves whenever the regulated gas may be subjected to thermal expansion. Chambers shall be sized to provide protection for piping and instrumentation and to accommodate the expansion of regulated materials. 15.04.500 Section 5003.2.2.2 Additional regulations for supply piping for health hazard materials. Section 5003.2.2.2 of the California Fire Code is amended to read as follows: 5003.2.2.2 Additional regulations for supply piping for health hazard materials. Supply piping and tubing for gases and liquids having a health hazard ranking of 3 or 4 in accordance with ASME B31.3 and the following: 1.Piping and tubing utilized for the transmission of toxic, highly toxic, or highly volatile corrosive liquids and gases shall have welded or brazed connections throughout except for connections within an exhausted enclosure if the material is a gas, or an approved method of drainage or containment is provided for connections if the material is a liquid. 2.Piping and tubing shall not be located within corridors, within any portion of a means of egress required to be enclosed in fire-resistance-rated construction or in concealed spaces in areas not classified as Group H Occupancies. Exception: Piping and tubing within the space defined by the walls of corridors and the floor or roof above or in concealed space above other occupancies when installed in accordance with Section 415.11.7.4 of the California Building Code as required for Group H5 occupancies. 3.All primary piping for toxic, highly toxic and moderately toxic gases shall pass a helium leak test of 1x10-9 cubic centimeters/second where practical, or shall pass testing in accordance with an approved, nationally recognized standard. Tests shall be conducted by a qualified “third party” not involved with the construction of the piping and control systems. 15.04.510 Section 5003.3.1 Unauthorized discharges. Section 5003.3.1 of the California Fire Code is amended to read as follows: 5003.3.1 Unauthorized discharges. In the event hazardous materials are released in quantities reportable under state, federal or local regulations or when there is a threatened release that presents a threat to health, property or the environment, the fire Docusign Envelope ID: 9D422E8D-6457-425E-A365-25F0361FFDE4 26 20251017_ms29 code official shall be notified immediately in an approved manner and the following procedures required in accordance with Sections 5003.3.1.1 through 5003.3.1.4. 15.04.520 Section 5003.5.2 Ventilation ducting. Section 5003.5.2 is added to the California Fire Code to read as follows: 5003.5.2 Ventilation ducting. Ducts venting hazardous materials operations shall be labeled with the hazard class of the material being vented and the direction of flow. 15.04.530 Section 5003.5.3 “H” Occupancies. Section 5003.5.4 is added to the California Fire Code to read as follows: 5003.5.3 “H” Occupancies. In “H” occupancies, all piping and tubing may be required to be identified when there is any possibility of confusion with hazardous materials transport tubing or piping. Flow direction indicators are required. 15.04.540 Section 5003.9.11 Fire extinguishing systems for workstations dispensing, handling or using hazardous materials. Section 5003.9.11 is added to the California Fire Code to read as follows: 5003.9.11 Fire extinguishing systems for workstations dispensing, handling or using hazardous materials. Combustible and non-combustible workstations which dispense, handle or use hazardous materials shall be protected by an approved automatic fire extinguishing system. Exception: Internal fire protection is not required for Biological Safety Cabinets that carry NSF/ANSI certification where quantities of flammable liquids in use or storage within the cabinet do not exceed 500 ml. 15.04.550 Section 5003.10.4 Elevators utilized to transport hazardous materials. Section 5003.10.4 of the California Fire Code is amended to read as follows: 5003.10.4 Elevators utilized to transport hazardous materials. 5003.10.4.1 When transporting hazardous materials, elevators shall have no other passengers other than in the individual(s) handling the chemical transport cart. 5003.10.4.1.1 When transporting cryogenic or liquefied compressed gases, there shall be no occupants in the elevator. 5003.10.4.2 Hazardous materials liquid containers shall have a maximum capacity of 20 liters (5.28 gal). 5003.10.4.3 Highly toxic, moderately toxic, and toxic gases shall be limited to a container Docusign Envelope ID: 9D422E8D-6457-425E-A365-25F0361FFDE4 27 20251017_ms29 of a maximum water capacity of 1 lb. 5003.10.4.4 When transporting cryogenic or liquefied compressed gases means shall be provided to prevent the elevator from being summoned to other floors. 15.04.560 Section 5004.2.1 Spill control for hazardous material liquids. Section 5004.2.1 of the California Fire Code is amended to read as follows: 5004.2.1 Spill control for hazardous material liquids. Rooms, buildings or areas used for storage of hazardous material liquids shall be provided with spill control to prevent the flow of liquids to adjoining areas. Floors in indoor locations and similar surfaces in outdoor locations shall be constructed to contain a spill from the largest single vessel by one of the following methods: 1.Liquid-tight sloped or recessed floors in indoor locations or similar areas in outdoor locations. 2.Liquid-tight floors in indoor and outdoor locations or similar areas provided with liquid-tight raised or recessed sills or dikes. 3.Sumps and collection systems, including containment pallets in accordance with Section 5004.2.3. 4.Other approved engineered systems. Except for surfacing, the floors, sills, dikes, sumps and collection systems shall be constructed of noncombustible material, and the liquid-tight seal shall be compatible with the material stored. When liquid-tight sills or dikes are provided, they are not required at perimeter openings having an open-grate trench across the opening that connects to an approved collection system. 15.04.570 Sections 5004.2.2 and 5004.2.2.2 and Table 5004.2.2 Secondary containment for hazardous material liquids and solids. Sections 5004.2.2 and 5004.2.2.2 of the California Fire Code are amended to read as follows: 5004.2.2 Secondary containment for hazardous material liquids and solids. Buildings, rooms or areas used for the storage of hazardous materials liquids or solids shall be provided with secondary containment in accordance with this section. Table 5004.2.2 is deleted in its entirety. [. . .] 5004.2.2.2 Incompatible Materials. Incompatible materials shall be separated from each Docusign Envelope ID: 9D422E8D-6457-425E-A365-25F0361FFDE4 28 20251017_ms29 other in independent secondary containment systems. 15.04.580 Section 5004.2.3 Containment pallets. Section 5004.2.3 of the California Fire Code is amended to read as follows: 5004.2.3 Containment pallets. Combustible containment pallets shall not be used inside buildings to comply with Section 5004.2 where the individual container capacity exceeds 55 gallons (208 L) or an aggregate capacity of multiple containers exceeds 1,000 gallons (3785 L) for liquids or where the individual container capacity exceeds 550 pounds (250 kg) or an aggregate of multiple containers exceeds 10,000 pounds (4540 kg) for solids. Where used as an alternative to spill control and secondary containment for outdoor storage in accordance with the exception in Section 5004.2, containment pallets shall comply with all of the following: 1.A liquid-tight sump accessible for visual inspection shall be provided; 2.The sump shall be designed to contain not less than 66 gallons (250L); 3.Exposed surfaces shall be compatible with material stored; Containment pallets shall be protected to prevent collection of rainwater within the sump of the containment pallet. 15.04.590 Section 5704.2.7.5.8 Overfill prevention. Section 5704.2.7.5.8 of the California Fire Code is amended to read as follows: 5704.2.7.5.8 Overfill prevention. An approved means or method in accordance with Section 5704.2.9.7.5 shall be provided to prevent overfill of all Class I, II and IIIA liquid storage tanks. Storage tanks in refineries, bulk plants or terminals regulated by Sections 5706.4 or 5706.7 shall have overfill protection in accordance with API 2350. An approved means or method in accordance with Section 5704.2.9.7.5 shall be provided to prevent the overfilling of Class IIIB liquid storage tanks connected to fuel-burning equipment inside buildings. Exception: Outside aboveground tanks with a capacity of 1320 gallons (5000 L) or less need only comply with Section 5704.2.9.7.5.1 (1.1) 15.04.600 Section 5704.2.7.5.9 Automatic and/or remote filling of tanks. Section 5704.2.7.5.9 is added to the California Fire Code to read as follows: 5704.2.7.5.9 Automatic and/or remote filling of tanks. Systems that remotely or automatically fill flammable or combustible liquid tanks shall be equipped with overfill Docusign Envelope ID: 9D422E8D-6457-425E-A365-25F0361FFDE4 29 20251017_ms29 protection, as approved by the fire code official, that sends an alarm signal to a constantly attended location and immediately stops the filling of the tank. The alarm signal and automatic shutoff shall be tested on an annual basis. Records of such testing shall be maintained on-site, and available for review, for a period of five (5) years. 15.04.610 Reserved 15.04.620 Section 6001.1 Site scope. Section 6001.1 of the California Fire Code is amended to read as follows: 6001.1 Site scope. The storage and use of highly toxic, moderately toxic and/or toxic materials shall comply with this chapter. Compressed gases shall also comply with Chapter 53. Exceptions: 1.Display and storage in Group M and storage in Group S occupancies complying with Section 5003.1 1. 2.Conditions involving pesticides or agricultural products as follows: 2.1. Application and release of pesticide, agricultural products and materials intended for use in weed abatement, erosion control, soil amendment or similar applications when applied in accordance with the manufacturer’s instruction and label directions. 2.2. Transportation of pesticides in compliance with the Federal Hazardous Materials Transportation Act and regulations thereunder. 2.3. Storage in dwellings or private garages of pesticides registered by the U.S. Environmental Protection Agency to be utilized in and around the home, garden, pool, spa and patio. 15.04.630 Section 6002.1 Definitions. Section 6002.1 is amended to read as follows: 6002.1 Definitions. The following terms are defined in Chapter 2: CONTAINMENT SYSTEM. CONTAINMENT VESSEL. EXCESS FLOW VALVE. HIGHLY TOXIC. MODERATELY TOXIC GAS OZONE-GAS GENERATOR. Docusign Envelope ID: 9D422E8D-6457-425E-A365-25F0361FFDE4 30 20251017_ms29 PHYSIOLOGICAL WARNING THRESHOLD. REDUCED FLOW VALVE. TOXIC. 15.04.640 Section 6004.1 Highly toxic, moderately toxic and toxic compressed gases. Section 6004.1 of the California Fire Code is amended to read as follows: 6004.1.1 The storage and use of highly toxic, moderately toxic, and toxic compressed gases shall comply with this section. 6004.1.1 Special limitations for indoor storage and use by occupancy. The indoor storage and use of highly toxic, moderately toxic, and toxic compressed gases in certain occupancies shall be subject to the limitations contained in Sections 6004.1.1.1 through 6004.1.1 .3. 6004.1.1.1 Group A, E, I or U occupancies. Toxic, moderately toxic and highly toxic compressed gases shall not be stored or used within Group A, E, I or U occupancies. Exception: Cylinders not exceeding 20 cubic feet (0.566 m3) at normal temperature and pressure (NTP) are allowed within gas cabinets or fume hoods. 6004.1.1.2 Group R occupancies. Toxic, moderately toxic, and highly toxic compressed gases shall not be stored or used in Group R occupancies. 6004.1.1.3 Offices, retail sales and classrooms. Toxic, moderately toxic and highly toxic compressed gases shall not be stored or used in offices, retail sales or classroom portions of Group B, F, M or S occupancies. Exception: In classrooms of Group B occupancies, cylinders with a capacity not exceeding 20 cubic feet (0.566 m3) at NTP are allowed in gas cabinets or fume hoods. 15.04.650 Sections 6004.2 and 6004.2.1 Indoor storage and use. Sections 6004.2 and 6004.2.1 of the California Fire Code are amended to read as follows: 6004.2 Indoor storage and use. The indoor storage and use of highly toxic, moderately toxic, and toxic compressed gases shall be in accordance with Sections 6004.2.1 through 6004.2.2.10.3. 6004.2.1 Applicability. The applicability of regulations governing the indoor storage and use of highly toxic, moderately toxic, and toxic compressed gases shall be as set forth in Sections 6004.2.1.1 through 6004.2.1.4. 15.04.660 Section 6004.2.1.1 and Table 6004.2.1.1 Quantities. Section 6004.2.1.4 and Table 6004.2.1.4 of the California Fire Code are added to read as follows: Docusign Envelope ID: 9D422E8D-6457-425E-A365-25F0361FFDE4 31 20251017_ms29 6004.2.1.1 Quantities not exceeding the maximum allowable quantity per control area. The indoor storage or use of highly toxic, moderately toxic, and toxic gases in amounts exceeding the minimum threshold quantities per control area set forth in Table 6004.2.1.4 but not exceeding maximum allowable quantity per control area set forth in Table 5003.1.1(2) shall be in accordance with Sections 5001, 5003, 6001, 6004.1, and 6004.4. Table 6004.2.1.1 Minimum Threshold Quantities for Highly Toxic, Moderately Toxic and Toxic Gases for Indoor Storage and Use Highly Toxic 20 cubic feet Moderately Toxic 405 cubic feet Toxic 405 cubic feet 15.04.670 Section 6004.4 through 6004.4.8.2 General indoor requirements. Section 6004.4 through 6004.4.8.2 of the California Fire Code is added to read as follows: 6004.4. General indoor requirements. The general requirements applicable to the indoor storage and use of highly toxic, moderately toxic, and toxic compressed gases shall be in accordance with Sections 6004.4 through 6004.4.8.2 6004.4.1 Cylinder and tank location. Cylinders shall be located within gas cabinets, exhausted enclosures or gas rooms. Portable and stationary tanks shall be located within gas rooms or exhausted enclosures. Exception: 1.Where a gas detection system is provided in accordance with 6004.4.8 6004.4.2. Ventilated areas. The room or area in which gas cabinets or exhausted enclosures are located shall be provided with exhaust ventilation. Gas cabinets or exhausted enclosures shall not be used as the sole means of exhaust for any room or area. 6004.4.3. Piping and controls. In addition to the requirements of Section 5003.2.2, piping and controls on stationary tanks, portable tanks, and cylinders shall comply with the following requirements: 1.Stationary tanks, portable tanks, and cylinders in use shall be provided with a means of excess flow control on all tank and cylinder inlet or outlet connections. Exceptions: Docusign Envelope ID: 9D422E8D-6457-425E-A365-25F0361FFDE4 32 20251017_ms29 1.Inlet connections designed to prevent backflow. 2.Pressure relief devices. 6004.4.4 Gas rooms. Gas rooms shall comply with Section 5003.8.4 and both of the following requirements: 1.The exhaust ventilation from gas rooms shall be directed to an exhaust system. 2.Gas rooms shall be equipped with an approved automatic sprinkler system. Alternative fire-extinguishing systems shall not be used. 6004.4.5 Treatment systems. The exhaust ventilation from gas cabinets, exhausted enclosures and gas rooms, required in Section 6004.4.1 shall be directed to a treatment system. The treatment system shall be utilized to handle the accidental release of gas and to process exhaust ventilation. The treatment system shall be designed in accordance with Sections 6004.2.2.7.1 through 6004.2.2.7.5 and Chapter 5 of the California Mechanical Code. Exceptions: 1.Highly toxic, moderately toxic, and toxic gases—storage. A treatment system is not required for cylinders, containers and tanks in storage where all of the following controls are provided: a.Valve outlets are equipped with gas-tight outlet plugs or caps. b.Hand wheel-operated valves have handles secured to prevent movement. c.Approved containment vessels or containment systems are provided in accordance with Section 6004.2.2.3. 2.Highly toxic, moderately toxic, and toxic gases —use. Treatment systems are not required for highly toxic, moderately toxic, and toxic gases supplied by stationary tanks, portable tanks, or cylinders where a gas detection system complying with Section 6004.4.8 and listed or approved automatic-closing fail-safe valves are provided. The gas detection system shall have a sensing interval not exceeding 5 minutes. Automatic- closing fail-safe valves shall be located immediately adjacent to cylinder valves and shall close when gas is detected at the permissible exposure limit (PEL) by a gas sensor monitoring the exhaust system at the point of discharge from the gas cabinet, exhausted enclosure, ventilated enclosure or gas room. 6004.4.5.1. Design. Treatment systems shall be capable of diluting, adsorbing, absorbing, containing, neutralizing, burning or otherwise processing the contents of the largest single vessel of compressed gas. Where a total containment system is used, the system shall be designed to handle the maximum anticipated pressure of release to the system when it reaches equilibrium. 6004.4.5.2. Performance. Treatment systems shall be designed to reduce the maximum Docusign Envelope ID: 9D422E8D-6457-425E-A365-25F0361FFDE4 33 20251017_ms29 allowable discharge concentrations of the gas to one-half immediate by dangerous to life and health (IDLH) at the point of discharge to the atmosphere. Where more than one gas is emitted to the treatment system, the treatment system shall be designed to handle the worst-case release based on the release rate, the quantity and the IDLH for all compressed gases stored or used. 6004.4.5.3. Sizing. Treatment systems shall be sized to process the maximum worst- case release of gas based on the maximum flow rate of release from the largest vessel utilized. The entire contents of the largest compressed gas vessel shall be considered. 6004.4.5.4 Stationary tanks. Stationary tanks shall be labeled with the maximum rate of release for the compressed gas contained based on valves or fittings that are inserted directly into the tank. Where multiple valves or fittings are provided, the maximum flow rate of release for valves or fittings with the highest flow rate shall be indicated. Where liquefied compressed gases are in contact with valves or fittings, the liquid flow rate shall be utilized for computation purposes. Flow rates indicated on the label shall be converted to cubic feet per minute (cfm/min) (m3/s) of gas at normal temperature and pressure (NTP). 6004.4.5.5 Portable tanks and cylinders. The maximum flow rate of release for portable tanks and cylinders shall be calculated based on the total release from the cylinder or tank within the time specified in Table 6004.2.2.7.5. Where portable tanks or cylinders are equipped with approved excess flow or reduced flow valves, the worst- case release shall be determined by the maximum achievable flow from the valve as determined by the valve manufacturer or compressed gas supplier. Reduced flow and excess flow valves shall be permanently marked by the valve manufacturer to indicate the maximum design flow rate. Such markings shall indicate the flow rate for air under normal temperature and pressure. 6004.4.6. Emergency power. Emergency power shall be provided for the following systems in accordance with Section 604: 1.Exhaust ventilation system. 2.Treatment system. 3.Gas detection system. 4.Smoke detection system. 6004.4.6.1. Fail-safe systems. Emergency power shall not be required for mechanical exhaust ventilation and treatment systems where approved fail-safe systems are installed and designed to stop gas flow. 6004.4.7. Automatic fire detection system. An approved automatic fire detection system shall be installed in rooms or areas where highly toxic, toxic, and moderately toxic compressed gases are stored or used. Activation of the detection system shall sound a local alarm. The fire detection system shall comply with Section 907. Docusign Envelope ID: 9D422E8D-6457-425E-A365-25F0361FFDE4 34 20251017_ms29 6004.4.8. Gas detection system. A gas detection system complying with Section 916 shall be provided to detect the presence of gas at or below the PEL or ceiling limit of the gas for which detection is provided. Exceptions: 1.A gas detection system is not required for toxic and moderately toxic gases when the physiological warning threshold level for the gas is at a level below the accepted PEL for the gas. 2.A gas detection system is not required for highly toxic, toxic, and moderately toxic gases where cylinders, portable tanks, and all non-continuously welded connects are within a gas cabinet or exhausted enclosures. 6004.4.8.1. Alarms. The gas detection system shall initiate a local alarm and transmit a signal to an approved location. 6004.4.8.2. Shut off of gas supply. The gas detection system shall automatically close the shut off valve at the source on gas supply piping and tubing related to the system being monitored for whichever gas is detected. Exception: Automatic shutdown is not required for highly toxic, moderately toxic, and toxic compressed gas systems where all of the following controls are provided: 1.Constantly attended / supervised. 2.Provided with emergency shutoff valves that have ready access. SECTION 2. The Council adopts the findings for local amendments to the California Fire Code, 2025 Edition, attached hereto as Exhibit "A" and incorporated herein by reference. SECTION 3. The Council finds that, with the exception of the changes codified at PAMC Sections 15.04.180, 260, 280, 295, 375, and 435, the changes or modifications to the California Fire Code adopted by this ordinance are substantially equivalent to changes or modifications that were previously filed by the governing body of the City and were in effect as of September 30, 2025, and are therefore exempt from the moratorium on new residential building standards imposed by Assembly Bill (AB) 130 (2025). To the extent that the changes codified at the PAMC sections listed in this finding are not substantially equivalent to changes or modifications previously filed and in effect as of September 30, 2025, they do not affect residential units and are therefore not subject to the AB 130 moratorium. SECTION 4. If any section, subsection, clause or phrase of this Ordinance is for any reason held to be invalid, such decision shall not affect the validity of the remaining portion or sections of the Ordinance. The Council hereby declares that it would have adopted the Ordinance and each section, subsection, sentence, clause or phrase thereof irrespective of the fact that any one or more sections, subsections, sentences, clauses or phrases be declared invalid. Docusign Envelope ID: 9D422E8D-6457-425E-A365-25F0361FFDE4 35 20251017_ms29 SECTION 5. The Council finds that this project is exempt from the provisions of the California Environmental Quality Act (“CEQA”), pursuant to Section 15061 of the California Guidelines, because it can be seen with certainty that there is no possibility that the amendments herein adopted will have a significant effect on the environment. SECTION 6. This Ordinance shall become effective on the commencement of the thirty-first day after the day of its adoption. INTRODUCED: NOVEMBER 3, 2025 PASSED: DECEMBER 1, 2025 AYES: BURT, LAUING, LYTHCOTT-HAIMS, RECKDAHL, STONE, VEENKER NOES: ABSENT: LU ABSTENTIONS: ATTEST: ____________________________ ____________________________ City Clerk Mayor APPROVED AS TO FORM: APPROVED: ____________________________ ____________________________ City Attorney or Designee City Manager ____________________________ Director of Planning and Development Services ____________________________ Fire Chief Docusign Envelope ID: 9D422E8D-6457-425E-A365-25F0361FFDE4 36 20251017_ms29 EXHIBIT A Findings for Local Amendments to the 2025 California Fire Code The following local amendments to the 2025 California Fire Code make modifications as authorized by the California Health and Safety Code. In accordance with Section 18941.5 of said Code, Findings are hereby made to show that such modifications or changes are reasonably necessary because of local climatic, geological or topographical conditions. I.PREAMBLE I.Findings of fact A. Pursuant to Section 17958.5 of the California Health and Safety Code, the report contained herein is submitted as the “Findings of Fact” document with regard to the adoption of the California Fire Code, 2025 Edition, and amendments. Under this adopting ordinance, specific amendments have been established which are more restrictive in nature than those adopted by the State of California (State Building Code Standards, State Housing and Community Development Codes) commonly referred to as California Code of Regulations, Titles 19, 24 and 25. B. These amendments to the California Fire Code, 2025 Edition, have been recognized by the City of Palo Alto (“City”) as tools for addressing the fire problems, concerns and future direction by which the authority can establish and maintain an environment which will afford a level of fire and life safety to all who live and work within the City’s boundaries. C. Under the provisions of Section 17958.5 of the Health and Safety Code, local amendments shall be based upon the following: climatic, geological/geographical, and topographical conditions. The findings of fact contained herein shall address each of these situations and shall present the local situation which, either singularly or in combination, caused the established amendments to be adopted. 1.Climactic Conditions: The City, on an average, experiences an annual rainfall of 16" - 18". This rainfall can be expected between October and April of each year. However, during the summer months there is little, if any, measurable precipitation. During this dry period the temperatures are usually between 70- 90 degrees with light to gusty westerly winds. These drying winds, combined with the natural vegetation which is dominant throughout the area, create a hazardous fuel condition which can cause, and has caused in the past, extensive grass and brush land fires. With more and more development encroaching into these wooded and grass covered areas, wind-driven fires could have severe consequences, as has been demonstrated on several occasions in Palo Alto and other Docusign Envelope ID: 9D422E8D-6457-425E-A365-25F0361FFDE4 37 20251017_ms29 areas of the state. Fires in structures can easily spread to the wildland as well as a fire in the wildland into a structure. Because of the weather patterns, a normal rainfall cannot always be relied upon. This can result in water rationing and water allocation systems, as demonstrated by the drought years of 1986- 1991. Water shortages can also be expected in the future due to the current water storage capacities and increased consumption. The water supply for the Palo Alto fire department makes use of automatic fire sprinkler systems feasible as a means to reduce our dependency on large volumes of water for fire suppression. 2. Geological & Geographical Conditions: Geographical Location. Palo Alto is located at the northern most part of Santa Clara County. Palo Alto is a major focus of the “Silicon Valley,” the center for an expanding and changing electronics industry, as well as pharmaceutical, biomedical, and genetic research. Seismic Location. Palo Alto is situated on alluvial solids between San Francisco Bay and the San Andreas Fault zone. The City’s location makes it particularly vulnerable to damage to taller and older structures caused by seismic events. The relatively young geological processes that have created the San Francisco Bay Area are still active today. Seismically, the city sits between two active earthquake faults (San Andreas and the Hayward/Calaveras), and numerous potentially active faults. Approximately 55% of the City’s land surface is in the high-to-moderate seismic hazard zones. Seismic and Fire Hazards. Fire following an earthquake has the potential of causing greater loss of life and damage than the earthquake itself. The majority of the City’s high-rise structures are located in seismic risk zones. Should a significant seismic event occur, Public Safety resources would have to be prioritized to mitigate the greatest threat, and may not be available for every structural fire. In such event, individual structures, including high-rise buildings, should be equipped to help in mitigating the risk of damage. Other variables may tend to intensify the situation: a.The extent of damage to the water system; b.The extent of isolation due to bridge and/or freeway overpass collapse; c.The extent of roadway damage and/or amount of debris blocking the roadways; d.Climatical conditions (hot, dry weather with high winds); e.Time of day will influence the amount of traffic on roadways and could intensify the risk to life during normal business hours; f.The availability of timely mutual aid or military assistance; g.Many high-rise structures are located near areas of high fire danger necessitating special Docusign Envelope ID: 9D422E8D-6457-425E-A365-25F0361FFDE4 38 20251017_ms29 precautions. Transportation. Palo Alto is dissected by a major state highway (El Camino Real) and two major freeways (I-280 and U.S. 101), which potentially could negatively affect response times of fire suppression equipment. Soil Conditions. Palo Alto lies at the southern end of San Francisco Bay and is built atop the alluvial deposits that surround the margins of the Bay. The alluvium was created by the flooding of many streams emptying into the San Francisco Bay depression, and from intermittent sea water inundation that has occurred over the last 2 or 3 million years. The areas closest to the Bay are overlain by unconsolidated fine silty clay, known as Bay Mud which varies in thickness from a few feet to as much as 30 feet. Generally, the older more stable alluvium is to the south and the younger less stable material is to the north. Bedrock lies beneath the area at depths of generally 300' or more. 3. Topographical Conditions: The findings of fact for the topographical element, as would be expected, are closely associated with the geological/geographical element. With the elevation changes within the district, development is of course following the path of least resistance, creating a meandering pattern. This then does not lend itself to a good systematic street and road layout, which would promote easy traffic flow. It has, in fact, resulted in few major crosstown thoroughfares which tend to be heavily congested, primarily during commute hours and seasonal periods of the year. This creates barriers which reduce the response time of fire equipment and other emergency services. The topography of the district is being burdened by major structures. Employment areas are throughout the district. The people who work in these complexes have added to the traffic congestion throughout the city, thereby reducing the fire department’s response time capabilities. Inherent delays caused by the traffic patterns to many of these types of projects, make it necessary to mitigate this problem by requiring additional built-in automatic fire protection systems to provide early detection and initial control until the arrival of the fire department. The topography of the district in much of the commercial and residential zones lies within or near a flood plane. Periodically, heavy rains and high tides cause region-wide flooding which not only delays response but also increases demands on fire personnel. The fire code amendments increase safeguards and initialize early response to help compensate for these physical delays. As a result of the findings of facts which identify the various climatic, geological/geographical and topographical elements, those additional requirements as specified in the amendments to adopting ordinance for the California Fire Code 2025 Edition, by the City of Palo Alto area are considered reasonable and necessary modifications. The experience of several disastrous fires Docusign Envelope ID: 9D422E8D-6457-425E-A365-25F0361FFDE4 39 20251017_ms29 within the city in addition to Santa Clara, Monterey, San Mateo, Alameda and Contra Costa counties have demonstrated the need for other fire protection features, the most significant of which was located in the Oakland/Berkeley Hills in which over 3,000 homes were destroyed and 25 human lives were lost. While it is clearly understood that the adoption of such regulations may not prevent the incidence of fire, the implementation of these various amendments to the Code may reduce the severity and potential of loss of life and property. II. Specific Findings for Local Amendments The majority of local amendments (those not specifically listed below) are made strictly to conform to other parts of the Palo Alto Municipal Code (PAMC) and for similar administrative purposes. Based upon the findings of fact described in section I, the City Council also makes the following specific findings regarding local climatic, geological, and topographic conditions related to local amendments to the California and International Fire Codes found in Chapter 15.04 of Title 15 of the Palo Alto Municipal Code (“PAMC”): 1.The local amendments contained in PAMC sections 15.4.030, 15.04.040, 15.04.050, 15.04.110, 15.04.130, and 15.04.140 are administrative in nature and do not require local topographical, geographical, or climatic findings. 2.The local amendments contained in PAMC sections 15.04.060 through 15.04.090, 15.04.150, 15.04.170, 15.04.260, and 15.04.440 through 15.04.670 - relating to general conditions for hazardous materials are necessary modifications to the California Fire Code flammable and hazardous materials sections because they maintain consistency with the Hazardous Materials Storage Ordinance which has been adopted county-wide since 1983. Requirements include safeguards such as monitoring, secondary containment, separation of non-compatibles which prevent incidents should a seismic event, unauthorized release or accident occur. See Findings 2 and 3 above - Geological and Topographical. 3.The local amendment contained in PAMC section 15.04.260- Immersion Heaters- is necessary as a fire control measure because it requires additional controls on process heating devices which are often activated when unattended. See Finding 2 above - Geological. 4.The local amendments contained in PAMC 15.04.180 and 15.04.280 through 15.04.340 relating to fire sprinkler systems are necessary for faster control of fires in the dense populated area and areas in an extended response time of our community to confine a fire to the area of origin rather than spread to neighboring structures. The modifications contained in these amendments provide additional fire extinguishing systems in new construction, major remodels, additions, and occupancy classification changes to help Docusign Envelope ID: 9D422E8D-6457-425E-A365-25F0361FFDE4 40 20251017_ms29 mitigate the problems identified in Findings 1, 2, and 3, above- Climatic, Geographical and Topographical. 5.The local amendment contained in PAMC section 15.04.320 - Floor control valves is necessary to provide fire extinguishing control devices that allow systems to remain partially in service while repairs or maintenance are ongoing. See Findings 1 and 2 above- Climatic and Geographical. 6.The local amendments contained in PAMC section 15.04.350 provides emergency lighting, where emergency lighting is required, in public restrooms regardless of size for public safety. See Findings 1, 2, and 3 – Climatic, Geographical and Topographical. 7.The local amendment contained in PAMC section 15.04.360 matches the requirements for exceptions for emergency escapes in basements/storm shelters in local amendment contained in section 16.04.360. See Findings 1 and 2 – Climatic and Geographical. 8.The local amendments contained in PAMC section 15.04.370 through 15.04.380 are recommendations from Santa Clara County Fire Marshals Association to decrease the fire hazard and risk of fire spread associated with commercial ESS installations and clarifying location for residential ESS to not interfere with emergency escapes or rescue openings. See Finding 3 above – Topographical. 9.The local amendments contained in PAMC sections 15.04.390 and 15.04.400 provide for additional fire and life safety measures during construction and demolition. See Findings 2 and 3, above- Geographical and Topographical. 10.The local amendments contained in PAMC sections 15.04.060 through 15.04.090, 15.04.150, 15.04.460, and 15.04.620 through 15.04.670 regarding toxic gases incorporate requirements initially established by the Model Toxic Gas Ordinance and California Fire Code. Administrative and restrictive measures include changes in definitions, quantities regulated, and utilizes County consensus guidelines established by other regional agencies which share similar climatic, geological/geographical, and topographical conditions. See Findings 1, 2 and 3, above- Climatic, Geographical and Topographical. 11.The local amendments added in PAMC section 15.04.160 - Roof guardrails at interior courts provides for additional fire and life safety measures for firefighters on buildings with unconventional lightwells. See Findings 2 and 3, above- Geographical and Topographical. 12.The local amendments contained in PAMC section 15.04.020 set forth construction and design provisions for residential property to mitigate the additional risk of fire. The modifications contained in this amendment provide for additional precautions against fire risks Docusign Envelope ID: 9D422E8D-6457-425E-A365-25F0361FFDE4 41 20251017_ms29 necessitated by the conditions listed in Findings 1, 2, and 3, above- Climatic, Geographical and Topographical. 13.The local amendment contained in PAMC section 15.04.120 is necessary to identify who has the authority and to establish the frequency to inspect buildings and premises. The modifications contained in this amendment provide for additional precautions to mitigate the problems identified in Findings 1, 2, and 3, above- Climatic, Geographical and Topographical. 14.The local amendment contained in PAMC section 15.04.190 is necessary to set forth a limit of the maximum number of false alarms the city of Palo Alto Fire Department will respond to. This measure is necessary to prevent fire department resources from responding to non- emergency situations thereby being unavailable to respond to an actual emergency associated with Climatic, Geographical and Topographical conditions listed in Findings 1, 2 and 3 above. 15.The local amendments added in PAMC sections 15.04.200 through 15.04.250 – The Fire Access Roadways and Dimensions requirements are necessary to provide access for effective, efficient and safe firefighting operations. These measures are necessary to prevent a delay in fire department resources responding to and having access to an emergency situation associated with Climatic, Geographical and Topographical conditions listed in Findings 1, 2 and 3 above. 16.The local amendments added in PAMC section 15.04.270 – Prohibitive Locations and 15.04.435 - Portable Unvented Heaters are necessary to restrict the use of portable outdoor gas-fired heating appliances and portable unvented heaters in specific locations as these appliances can be a fire hazard that may also contribute to the uncontrolled spread of fire as a result of the Climatic, Geographical, and Topographical conditions described in Findings 1, 2, and 3 above. 17.The local amendment added in PAMC section 15.04.260 relating to the protection of energy storage systems is necessary to prevent potential damage and fire that may also contribute to the uncontrolled spread of fire as a result of the Climatic, Geographical, and Topographical conditions described in Findings 1, 2, and 3 above. Docusign Envelope ID: 9D422E8D-6457-425E-A365-25F0361FFDE4 Certificate Of Completion Envelope Id: 9D422E8D-6457-425E-A365-25F0361FFDE4 Status: Completed Subject: ORD 5682 - California Fire Code (2025 Edition) with Local Amendments and Related Findings Source Envelope: Document Pages: 41 Signatures: 6 Envelope Originator: Certificate Pages: 2 Initials: 0 Christine Prior AutoNav: Enabled EnvelopeId Stamping: Enabled Time Zone: (UTC-08:00) Pacific Time (US & Canada) 250 Hamilton Ave Palo Alto , CA 94301 Christine.Prior@PaloAlto.gov IP Address: 165.225.242.91 Record Tracking Status: Original 12/3/2025 1:37:11 PM Holder: Christine Prior Christine.Prior@PaloAlto.gov Location: DocuSign Security Appliance Status: Connected Pool: StateLocal Storage Appliance Status: Connected Pool: City of Palo Alto Location: Docusign Signer Events Signature Timestamp Madeleine Salah Madeleine.Salah@paloalto.gov Deputy City Attorney City of Palo Alto Security Level: Email, Account Authentication (None) Signature Adoption: Pre-selected Style Using IP Address: 170.85.54.99 Sent: 12/3/2025 2:47:28 PM Viewed: 12/3/2025 4:47:31 PM Signed: 12/3/2025 4:48:29 PM Electronic Record and Signature Disclosure: Not Offered via Docusign Stephen Lindsey Stephen.Lindsey@paloalto.gov Deputy Chief Security Level: Email, Account Authentication (None)Signature Adoption: Pre-selected Style Using IP Address: 165.225.242.82 Sent: 12/3/2025 4:48:30 PM Viewed: 12/4/2025 4:19:11 PM Signed: 12/4/2025 4:25:29 PM Electronic Record and Signature Disclosure: Not Offered via Docusign Jonathan Lait Jonathan.Lait@paloalto.gov Director, Planning and Development Services City of Palo Alto Security Level: Email, Account Authentication (None) Signature Adoption: Pre-selected Style Using IP Address: 165.225.242.87 Sent: 12/4/2025 4:25:30 PM Viewed: 12/4/2025 5:48:35 PM Signed: 12/4/2025 5:48:45 PM Electronic Record and Signature Disclosure: Not Offered via Docusign Ed Shikada Ed.Shikada@paloalto.gov City Manager City of Palo Alto Security Level: Email, Account Authentication (None) Signature Adoption: Pre-selected Style Using IP Address: 199.33.32.254 Sent: 12/4/2025 5:48:46 PM Viewed: 12/8/2025 8:49:19 AM Signed: 12/8/2025 8:49:26 AM Electronic Record and Signature Disclosure: Not Offered via Docusign Signer Events Signature Timestamp Ed Lauing Ed.Lauing@paloalto.gov Security Level: Email, Account Authentication (None) Signature Adoption: Pre-selected Style Using IP Address: 2601:647:6880:a6f0:6c64:7f7a:1bc3:6a5e Sent: 12/8/2025 8:49:28 AM Viewed: 12/8/2025 10:35:42 AM Signed: 12/8/2025 10:36:48 AM Electronic Record and Signature Disclosure: Not Offered via Docusign Mahealani Ah Yun Mahealani.AhYun@paloalto.gov City Clerk Security Level: Email, Account Authentication (None)Signature Adoption: Pre-selected Style Using IP Address: 2601:640:8e80:6e70:c466:d063:3596:ebb2 Sent: 12/8/2025 10:36:50 AM Viewed: 12/9/2025 11:09:38 AM Signed: 12/9/2025 11:10:03 AM Electronic Record and Signature Disclosure: Not Offered via Docusign In Person Signer Events Signature Timestamp Editor Delivery Events Status Timestamp Agent Delivery Events Status Timestamp Intermediary Delivery Events Status Timestamp Certified Delivery Events Status Timestamp Carbon Copy Events Status Timestamp Witness Events Signature Timestamp Notary Events Signature Timestamp Envelope Summary Events Status Timestamps Envelope Sent Hashed/Encrypted 12/3/2025 2:47:28 PM Certified Delivered Security Checked 12/9/2025 11:09:38 AM Signing Complete Security Checked 12/9/2025 11:10:03 AM Completed Security Checked 12/9/2025 11:10:03 AM Payment Events Status Timestamps