HomeMy WebLinkAbout2014-08-04 Ordinance 5263140423 dm 0160077
circuit; (4) 50 ampere wiring; terminating in (5) a 50 ampere NEMA
receptacle in a covered outlet box.
(d) EVSE Installed. "EVSE Installed" shall mean an installed Level 2 EVSE.
A5.106.5.3.2 Non-Residential Structures Other than Hotels. The following
standards apply newly constructed non-residential structures other than hotels.
(a) In general. The property owner shall provide Conduit Only, EVSE-Ready
Outlet, or EVSE Installed for at least 25% of parking spaces, among which at
least 5% (and no fewer than one) shall be EVSE Installed.
(b) Accessible spaces. The percentage calculations and substantive
requirements imposed by this section shall be applied separately to
accessible parking spaces. Parking at accessible spaces where an EVSE is
installed shall not be limited to electric vehicles.
(c) Minimum total circuit capacity. The property owner shall ensure sufficient
circuit capacity, as determined by the Chief Building Official, to support a
Level 2 EVSE in every location where Circuit Only, EVSE-Ready Outlet or
EVSE Installed is required.
(d) Location. The EVSE, receptacles, and/or raceway required by this section
shall be placed in locations allowing convenient installation of and access to
EVSE. Location of EVSE or receptacles shall be consistent with all City
guidelines, rules, and regulations.
A5.106.5.3.3 Hotels. The following standards apply newly constructed hotels.
(a) In general. The property owner shall provide Conduit Only, EVSE-Ready
Outlet, or EVSE Installed for at least 30% of parking spaces, among which at
least 10% (and no fewer than one) shall be EVSE Installed.
(b) Accessible spaces. The percentage calculations and substantive
requirements imposed by this section shall be applied separately to
accessible parking spaces. Parking at accessible spaces where an EVSE is
installed shall not be limited to electric vehicles.
(c) Minimum total circuit capacity. The property owner shall ensure sufficient
circuit capacity, as determined by the Chief Building Official, to support a
Level 2 EVSE in every location where Circuit Only, EVSE-Ready Outlet or
EVSE Installed is required.
(d) Location. The EVSE, receptacles, and/or raceway required by this section
shall be placed in locations allowing convenient installation of and access to
4